Operation, Changing the operating set point, Setting combustion – Fulton Caliber (CAL) Condensing Hydronic Boiler User Manual

Page 39

Advertising
background image

Questions? Please Contact Your Local Manufacturer’s Representative

SECTION 3

CAL-IOM-2013-1001

OPERATION

3-5

!

WARNING

Non-Fulton product information is for
reference purposes only. No Fulton
document should substitute for full
review of documentation available
from the component manufacturer.

4

CAUTION

When making changes to the controls
profi le, a combustion analyzer is
required.

equipment. Caliber boilers should be operated and controlled so that the boiler
cycles less than 12,000 times per year.

Outlet water temperature, fan speed and set point are displayed on the SOLA
touch screen display on the front of the boiler. Figure 14 shows a sample Status
Screen display on the SOLA control.

CHANGING THE OPERATING SET POINT

From the main screen, perform the following steps:

1. Tap

Confi gure.

2. Tap

Central Heat Confi guration.

3. Tap

CH Set Point.

4. Tap

Clear.

5. Enter the New Set Point.

6. Tap

OK.

7. Tap the escape arrow in top right hand corner (see Figure 15).

SETTING COMBUSTION

To Set Combustion, perform the following steps:

1. Obtain the following tools: Calibrated combustion analyzer, manometer to

measure inlet gas pressure.

2. From home screen tap Operation.

FIGURE 14 - SAMPLE STATUS SCREEN OF SOLA CONTROL