FEC DSP1500 (SAN3) User Manual
Page 3

enFORCE
Operation Manual
PAGE 4 - 3
Chapter 4: System Setup and Wiring
4.2 SAN Unit Design and Mounting Dimensions
SAN units must be mounted with a minimum clearance of 12mm on each side to allow proper heat
dissipation. Cable connections on the front of the units require 100mm of clearance.
Allow a minimum of 100mm clearance on the bottom of each controller for cable hook up when
updating firmware.
SAN units must be located a minimum of 600mm from any high transient voltage power source.
Mounting: Top
(1) place
#8-32 screw
Bottom (2) places
#8-32 screw
Weight: SAN3-24S – 1.4 kg
SAN3-40S – 1.8 kg
The diagram shown above shows the dimensions of the SAN3-40S.
The protrusion of the heat sink plate (14mm) is on the SAN3-40S only, therefore the width of the
SAN3-24S is 60mm as opposed to 74mm.
SAN3-24S, SAN3-40S