Chapter 4: System Setup and Wiring

4.3 Calculating Circuit Protection









The chart above shows nominal motor ratings for standard press motors, along with the power
requirements for each SAN unit. Use the formula below to calculate transformer secondary fuse or
circuit breaker sizes.



Transformer (VA)

1.5 x Secondary Voltage 3 = Secondary Fuse Size



Example:


1000 (VA)

1.5 x 200 VAC 3 = 4.33 Amps (Use 5 Amp Fuses)*



* Use a fuse or circuit breaker with the next available highest rating. Due to the high inrush current
at power up, it is recommended to use “Slow Blow” type fuses or fuses rated for motor loads such
as Bussman type FRS or FRN.

RATED VALUES FOR CALCULATING CIRCUIT PROTECTION

MOTOR

# OF SAN3 UNITS

KVA PER

MOTOR TYPE

WATTAGE

SAN3 UNIT

PER 1 KVA

SAN3 UNIT

R1

60

SAN3-24S

8

.125

R2

80

SAN3-24S

6

.167

R3

200

SAN3-40S

2.5

.40

R4

1500

SAN3-120S

0.5

2.0

R5

3000

SAN3-120S

0.25

4.0