Detector zone wiring, Detector – Fire Fighting Enterprises FIRERAY 100R User Manual

Page 4

Advertising
background image

For connection of multiple conventional Detectors to a zone:





































Note 1 – This component is the Fire Resistor, and its value is specified by the Fire Control
Panel Manufacturer. For US installations it is typically a short circuit.

Note2 – Schottky Diode (60Volt, 1 Amp typical; must be UL listed for installations meeting
NFPA72)

EOL – End of Line component – supplied by the Fire Control Panel manufacturer

See note 2

COM (BLUE)

NO (YELLOW)

COM (WHITE)

NC (GREEN)

Detector

ZONE WIRING

See note 1

Fire Relay

Trouble Relay

10.2 to 30 Volts DC (RED)

0V (BLACK)

PSU

EOL

COM (BLUE)

NO (YELLOW)

COM (WHITE)

NC (GREEN)

Detector

See note 1

Fire Relay

Trouble Relay

10.2 to 30 Volts DC (RED)

0V (BLACK)