8. Servicing and Maintenance

During Operating Mode, the following states will be indicated:

 Normal (no Fault or Fire) – Amber LED will flash every 10 seconds (EN approved model)

or not flash at all (UL approved model)

 Fire/Alarm – Red LED will be on continuously, and Fire Relay will close

 Fault – Amber LED on continuously, and Fault Relay will open

 Compensation Fault – Amber LED flashes every 2 seconds

A Compensation Fault will occur when the Detector can no longer compensate for signal
loss due to dust/dirt build-up on the lenses and/or Reflector. A Compensation Fault can be
cleared by cleaning the Reflector and Detector lenses using a dry lint-free cloth, and then re-
aligning the beam. Compensation Faults can be avoided by periodic cleaning of the Reflector
and Detector before compensation limit is reached.


9. Technical Data

 Operating Range (50 metre Detector)

5 to 50 metres

 Operating Range (100 metre Detector)

50 to 100 metres

 Supply Voltage limits

10.2Vdc to 30Vdc

 Quiescent Current (no LED’s illuminated) <4mA

Alarm/Fault

Current

<15

mA

 Power Down Reset Time

10 seconds

 Operating Temperature (EN)

-10

C to 55C

 Operating Temperature (UL)

32

F to 100F

Relative

Humidity 93%

(non-condensing)

 Tolerance to Beam Misalignment at 35% Detector  1.0, Prism  5.0

Fire

Alarm

Thresholds

2.50dB

(25%), 3.74dB (35%), 6.02dB (50%)

Optical

Wavelength

880nm

 Head Maximum Size

Width 130mm, Height 210mm, Depth 120mm

Weight

770

gms

IP

rating

IP50





22318.18.06-EN