Alignment process flow diagram – Fire Fighting Enterprises FIRERAY 100R User Manual

Page 6

Advertising
background image

Amber

Constant
AMBER

Red

Red

Amber

Neither

Alignment Process Flow Diagram:





















































Wait until both LED’s stop

flashing (up to 30 seconds)

Return to Prism
Targeting Mode

Slowly turn the

thumbwheel in the

same direction

Reverse the

direction of the

thumbwheel

Exit Alignment

Mode and enter

Operating Mode

Select alignment mode AMBER

LED will illuminate for

5 seconds

LED

flashing?

Slowly adjust a thumbwheel in

one direction and observe the

LEDs

LED

flashing?

For optimum alignment,

deflection of the beam in all

four planes should cause

the Amber LED to flash first

Repeat the

process for the

other

thumbwheel

Both

thumbwheels

adjusted?

No

Yes

Stop turning the

thumbwheel and wait

for the Red LED to

stop flashing

Stop turning the

thumbwheel

Advertising