Wire Gauge Factoring

1.1 Remote Power Supply

 The Magnalock requires adequate voltage and current for proper operation.

 Resistance is created by the length and gauge (size) of the wire being used.

 An accurate estimated distance from the power supply to the opening is crucial.

 For superior operation the correct size gauge wire must be used.

 The devices used operate the best with the least amount of resistance on the source.

 Using the correct gauge wires protects against large voltage and current (load) losses.

 The gauge is determined by the wire distance, voltage and current of all devices.


1.2 Determining Wire Gauge

 Follow Example A (12VDC system) and Example B (24VDC system) below.

 Use Tables 1 and Table 2 to choose the correct wire gauge for the application.


1.2.1 Example A: (12VDC system)

Devices Used

Amps (12VDC)

Progressive Totals

M62 Magnalock

0.250

0.250

DK-26 Access

0.160

0.410

XMS Motion

0.050

0.460

EEB2 Timer

0.025

0.485

Total Current Rounded Up (Table 1)

0.600A

Using Table 1 (12VDC) Find: - Current Draw

.600 Amps

- Wire Distance

200 Feet (One-Way)

Solution: 18 Gauge is indicated for proper installation


1.2.2 Example B: (24VDC system)








Using Table 2 (24VDC) Find: - Current Draw

.400 Amps

- Wire Distance 1000 Feet (One-Way)

Solution: 14 Gauge is indicated for proper installation

Devices Used

24VDC Amps

Progressive Totals

M82 Magnalock

0.200

0.200

TSB Touch Bar

0.025

0.225

DK-11 Access

0.070

0.295

XDT-24 Delay

0.050

0.345

MK Bypass/Reset

0.020

0.365

Total Current Rounded Up (Table 2)

0.400A