BondSTAT Sensor status wiring description

 The green and white wires supply electrical connection when the lock is ON and secure.

 The orange and white wires supply electrical connection when the lock OFF or unsecure.

5.3.5

DPS – Door Position Sensor status wiring description

 The blue and yellow wires supply electrical connection when the door condition is closed.

 The brown and yellow wires supply electrical connection when the door condition is open.

5.3.6

Double Door Status Wiring – BondSTAT

When two Magnalocks are used for double door installation the BondSTAT contacts should be
wired in series for proper reporting. Connect the green wire of one lock to the white wire of the
other as shown below in Figure 16.

Figure 16

5.3.7

Double Door Status Wiring – DPS

When two Magnalocks are used for double door installation the DPS contacts should be wired in
series for proper reporting. Connect the blue wire of one lock to the yellow wire of the other as
shown below in Figure 17.

Figure 17

5.3.8

Emergency Release

Magnalocks are often wired into a system for quick release in case of emergency. Manual
switching or automatic triggering from a fire alarm system is practical. It is the user's
responsibility to correctly hookup the Magnalock according to the instructions. It is
recommended to use a switch or relay to perform break of power. Securitron power supplies

have terminals for the interconnection of such emergency release switches.

THE END USER & INSTALLER ARE LIABLE FOR FIRE & BUILDING CODES COMPLIANCE

6. SPECIALIZED MOUNTING BRACKETS

ASB – Aluminum Shim Bracket The ASB bracket is designed for 1/2” [12.7mm]

blade stop and/or weather trim clearance mounting of Magnalocks on aluminum frame
glass doors.

CWB – Concrete/Wood Header Bracket – The CWB bracket is designed for mounting

Magnalocks on concrete filled and/or wood headers.

FMK-SL & FMK-SW – FLEX-MOUNT Kit The FMK (FLEX-MOUNT) bracket kits are

designed to install on most gate applications. Adapts to round or square posts from 1”
[25.4mm] to 3” [76.2mm]. The FMK-SL is designed for slide gate type applications. The
FMK-SW is designed for swing gate type applications.

GDB – Glass Door Bracket The GDB bracket is designed for mounting a Model 32 or

Model 62 strike to solid-type framed and unframed glass doors. An AKG adhesive kit used

for bonding.

HEB Bracket – The HEB is a 90 degree bracket designed to extend the door stop and

create a flat surface for mounting the Magnalock.

HEB-3G Bracket – The HEB-3G bracket is a 90 degree bracket designed for mounting to

solid-type framed and unframed glass headers. An AKG adhesive kit used for bonding.