Securitron SAM User Manual

Page 14

Advertising
background image

PN# 500-10440

Page 14

Rev. F, 02/12

Problem

DPS Does Not Report Door Status

Points of Reference

Check strike mounting for proper alignment

Table A / Section 5.6.6

Check for proper door closure Section

8.1

Check for proper voltage/current on switch

Section 2

Solution

Check resettable protection device

Section 1

Problem

The Magnalock Does Not Release

Points of Reference

Make sure no voltage is present at Magnalock

Section 2

Make sure the Magnalock is not drawing current

Section 2

Check if the strike is sticky and hard to release

Section 8

Solution

Check the Magnalock and strike for obstructions

and that contact surfaces are properly cleaned

Section 8

Problem

The Magnalock is Dirty or Rusty

Points of Reference

Solution

Improper cleaning – Maintenance Equipment

Section 8

Problem

Electronic Noise Interference with

Access Control System

Points of Reference

Solution

Check for voltage from Magnalock to door frame.

There should be no voltage present.

Section 2

IF PROBLEMS PERSIST CALL SECURITRON TOLL FREE

(800) MAG-LOCK

(800) 624-5625

Appendix B
Wire Gauge Factoring
1.1 Remote Power Supply
 The Magnalock requires adequate voltage and current for proper operation.

 Resistance is created by the length and gauge (size) of the wire being used.

 An accurate estimated distance from the power supply to the opening is crucial.

 For superior operation the correct size gauge wire must be used.

 The devices used operate the best with the least amount of resistance on the source.

 Using the correct gauge wires protects against large voltage and current (load) losses.

 The gauge is determined by the wire distance, voltage and current of all devices.

1.2 Determining Wire Gauge
 Follow Example A (12VDC system) and Example B (24VDC system) below.

 Use Tables 1 and Table 2 to choose the correct wire gauge for the application.

1.2.1 Example A: (12VDC system)

Devices Used

Amps (12VDC)

SAM Magnalock

0.320

DK-26 Access

0.160

XMS Motion Detector

0.050

EEB2 Timer

0.025

Total Current (0.555A) Rounded Up =

0.600A

Using Table 1 (12VDC) Find: - Current Draw

.600 Amps

- Wire Distance

200 Feet [61m] (One-Way)

Solution: 18 Gauge is indicated for proper installation