Important – Securitron SAM User Manual

Page 15

Advertising
background image

PN# 500-10440

Page 15

Rev. F, 02/12

1.2.2 Example B: (24VDC system)






Using Table 2 (24VDC) Find: - Current Draw

.600 Amps

- Wire Distance 1000 Feet [305m] (One-Way)

Solution: 14 Gauge is indicated for proper installation


TO SOLVE: INTERSECT ROW (Total Current Draw) and INTERSECTING COLUMN (One-
Way Wire Distance).

1.00A

20

Gauge

18

Gauge

16

Gauge

14

Gauge

14

Gauge

12

Gauge

10

Gauge

10

Gauge

8

Gauge

.800A

22

Gauge

18

Gauge

18

Gauge

16

Gauge

14

Gauge

12

Gauge

10

Gauge

10

Gauge

8

Gauge

.600A

22

Gauge

20

Gauge

18

Gauge

18

Gauge

16

Gauge

14

Gauge

14

Gauge

12

Gauge

10

Gauge

.400A

22

Gauge

22

Gauge

20

Gauge

18

Gauge

18

Gauge

16

Gauge

14

Gauge

14

Gauge

12

Gauge

.300A

24

Gauge

22

Gauge

22

Gauge

20

Gauge

18

Gauge

18

Gauge

16

Gauge

14

Gauge

14

Gauge

C

U
R
R

E

N

T

.200A

24

Gauge

22

Gauge

22

Gauge

22

Gauge

20

Gauge

18

Gauge

18

Gauge

16

Gauge

14

Gauge

50’

[15m]

100’

[30m]

150’

[46m]

200’

[61m]

300’

[91m]

400’

[122m]

500’

[152m]

750’

[229m]

1000’

[305m]

12VDC

WIRE DISTANCE

Table 1

1.00A

22

Gauge

20

Gauge

20

Gauge

18

Gauge

16

Gauge

14

Gauge

14

Gauge

12

Gauge

10

Gauge

.800A

22

Gauge

22

Gauge

20

Gauge

18

Gauge

18

Gauge

16

Gauge

14

Gauge

14

Gauge

12

Gauge

.600A

24

Gauge

22

Gauge

22

Gauge

20

Gauge

18

Gauge

18

Gauge

16

Gauge

14

Gauge

14

Gauge

.400A

24

Gauge

22

Gauge

22

Gauge

22

Gauge

20

Gauge

18

Gauge

18

Gauge

16

Gauge

14

Gauge

.300A

24

Gauge

24

Gauge

22

Gauge

22

Gauge

22

Gauge

20

Gauge

20

Gauge

18

Gauge

16

Gauge

C

U
R

R

E

N

T

.200A

24

Gauge

24

Gauge

24

Gauge

22

Gauge

22

Gauge

22

Gauge

20

Gauge

20

Gauge

18

Gauge

50’

[15m]

100’

[30m]

150’

[46m]

200’

[61m]

300’

[91m]

400’

[122m]

500’

[152m]

750’

[229m]

1000’

[305m]

24VDC

WIRE DISTANCE

Table 2

The Wire Distance indicated on the table above represents a 2-wire “One-Way” length from
the power supply source to entryway installation area.

The Gauge values specified on the table above represent a 2-wire “Round Trip” length from

the power supply source to entryway installation and returning back to the power supply
source.

IMPORTANT

THE 200’ [61m] WIRE RUN IN EACH TABLE FACTORS A 400’ [122m] ROUND TRIP


Devices Used

24VDC Amps

SAM Magnalock

0.320

DK-11 Access

0.070

XDT-24 Delay

0.050

Total Current (0.440A) Rounded Up =

0.600A