Securitron iMXDa_iEXDa_CH INSTALLATION User Manual

Page 11

Advertising
background image

P/N 500-22155

Page 11

Rev. A, 11/12

Operation

8 Position DIP

Directive

SW1 SW2 Seconds

Factory

Default
Setting

California

setting

Chicago
settings

OFF OFF zero

ON OFF

1

√ fixed

√ fixed

OFF ON

2

~ NDA ~

Nuisance Delay

Alarm

Matrix

ON ON

3


SW3

Cycle

Time

OFF 15

√ fixed

√ fixed

~ IRA ~

Irrevocable Alarm

ON 30

SW4 SW5 Seconds

OFF OFF zero

√ fixed

ON OFF

5

OFF ON

10

~ BDT ~

Bypass Delay Time

(External Only)

Matrix

ON ON 15

SW6 Function

OFF Disabled

√ fixed

~ PAR ~

Post Alarm

Reminder

ON Enabled

SW7

Function

OFF Disabled

√ fixed

~ BEA ~

Bypass Expiration

Alarm

ON Enabled

SW8

Function

OFF Manual

√ fixed

~ MDR ~

Manual/Delayed

Relock

ON

Delayed

√ fixed

Table A

DIP Switch Settings Matrix



NDA (Nuisance Delay Alarm) – DIP SW1 and SW2
NDA is a zero, 1, 2 or 3 second nuisance or warning delay (revocable) which initiates when door

movement is detected. When triggered the local alarm will sound (pulsing tone). The factory
default setting is zero seconds and is changed via DIP switch settings of SW1 and SW2. (This
setting is fixed to 1 second on the Chicago and California versions)

IRA (Irrevocable Alarm) – DIP SW3
IRA is an irrevocable alarm which initiates when door movement is detected. Once initiated the
complete delay cycle must expire prior to reset. This is a set 15 or 30 second total alarm time
cycle including any NDA time. The audible alarm sounds until the IRA expires. The factory
default setting is 15 seconds but can be changed to 30 seconds by changing DIP switch SW3.

(This setting is fixed to 15 seconds on the Chicago and California versions)


BDT (Bypass Delay Time) – DIP SW4 and SW5
BDT is an external switch bypass function only. Once triggered, a set zero, 5, 10 or 15 second
release time is initiated. The factory default setting is zero but it can be set to 5, 10 or 15

second (trailing edge trigger) by changing DIP switches SW4 and SW5. (This setting is fixed to
zero on the Chicago version)


PAR (Post Alarm Reminder) – DIP SW6
PAR is an audible alarm indicating the lock has completed an alarm cycle. After 5 seconds the
internal alarm will beep rapidly 3 times followed by 5 seconds of silence and will repeat until
reset. The factory default setting is off but PAR can be turned on with DIP switch SW6. Note:
This feature will not operate if a voltage is maintained on the “RS” terminal (See
Figure 13)
. (This setting is disabled on the Chicago version)