All wiring to the installed unit is made to the main terminal strip on the PC board inside the wire
access compartment. See Appendix B for wire gage size calculations. Further user-specific
(control) wiring connections are described in Section 6.3 - Control Wiring.
Power Supply Connections
Figures 7, 8 and 9 illustrate the proper electrical wiring required for connecting the
iMXDa/iEXDa to various Securitron power supplies, for 1 Amp see Figure 7 for the larger 2 to 15
Amp Securitron power supplies utilizing the CCS-4 or CCS-8 see Figures 8 and 9.
ALWAYS REFER TO THE MANUFACTURER’S PRODUCT MANUAL FOR PROPER
CONNECTION AND IMPLEMENTATION OF THE POWER SUPPLY BEING USED.
BATTERY BACK-UP IS NOT ALLOWED BY BUILDING CODES FOR INSTALLATIONS THAT
REQUIRE THE LOCK TO RELEASE THE DOOR UPON LOSS OF POWER.
(SEE APPENDIX D)
Figure 7
Connections for 1 Amp Power Supply (BPS-12-1/BPS-24-1)