APPENDIX B
Wire Gauge Factoring
Remote Power Supply

 The iMXDa/iEXDa requires adequate voltage and current for proper operation.

 Resistance is created by the length and gauge (size) of the wire being used.

 An accurate estimated distance from the power supply to the opening is crucial.

 For optimum operation the correct size gauge wire must be used.

 The devices used operate the best with the least amount of resistance on the source.

 Using the correct gauge wires protects against large voltage and current (load) losses.

 The gauge is determined by the wire distance, voltage and current of all devices.

Determining Wire Gauge

 Follow Example A (12VDC system) and Example B (24VDC system) below.

 Use Table B-1 and Table B-2 to determine the correct wire gauge for the application.

Example A: (an iMXDa used in a 12VDC system)

Devices Used

Amps (12VDC)

Progressive Totals

iMXDa

0.370

0.370

DK-26 Access

0.160

0.530

MK Bypass/Reset

0.020

0.550

Total Current Rounded Up (Table 1)

0.600A


Using Table B-1 (12VDC) Find: - Current Draw .600 Amps

- Wire Distance 200 Feet (One-Way)

Solution: 18 Gauge is indicated for proper installation

Example B: (an iEXDa used in a 24VDC system)







Devices Used

24VDC Amps

Progressive Totals

iEXDa

0.270

0.270

TSB Touch Bar

0.025

0.295

DK-11 Access

0.070

0.365

Total Current Rounded Up (Table 2)

0.400A