G. pump selection – HTP FP-40SC User Manual

Page 25

Advertising
background image

25


G. PUMP SELECTION


When selecting a pump, there are two basic solar designs to consider: pressure glycol and closed loop
drain back.

In pressure glycol systems, two factors determine pipe size. These are:

• Flow rate in gpm (gallons per minute)
• Head loss


In drain back systems, an additional factor must be considered along with the previous two:

• Lift

Each collector has a nominal flow rate of between .8 and 1.5 gpm.

When determining head loss, consider the following:

• Head loss pumping through the collector(s)

• Head loss pumping through piping and fittings

• Head loss pumping through a heat exchanger
• *Drain back only: Determine the vertical lift from the water level in the drain back tank to the top of

the solar panels (vertical lift is the same as head loss).


Refer to the chart below for pressure drop figures with a 40% glycol solution. When using distilled water
as HTF, there is a further 20% reduction in pressure drop.

NOTE: To convert psi to head feet, multiply psi by 2.31 and divide total by specific gravity (1 for water,
1.02 for 30% propylene glycol, 1.04 for 50% propylene glycol).

Table 4 – Pressure drop. This chart applies from 1 to 8 collectors. Do not multiply for multiple collectors.


NOTE ON CHART (Table 3): To figure feet of head, multiply pressure drop by 2.31.
For example:

1. FP-40SC at 3 gpm = 1.5 per panel and .071 psi = .071 for 2 panels at 3 gpm.
2. FP-40SC at 12 gpm = 1.5 per panel and .071 psi = .071 for 8 panels at 12 gpm.

Advertising
This manual is related to the following products: