IAI America PCON-CFA User Manual

Page 135

Advertising
background image

3. SCON-CA/CF

A

129

(12) Zone 1 (ZONE1)

PLC input signal

Zone 2 (ZONE2)

PLC input signal

Position zone (PZONE)

PLC input signal

These signals are turned ON when the current position of the actuator is within the set area and turned OFF
when the current position is out of the set area.


[1] Zone 1, Zone 2

The zone is set using the user parameters.
The Zone 1 Signal is set using the parameter No. 1 “Zone Boundary 1 “+” Side” and No. 2 “Zone Boundary
1 “–“ Side”.
The Zone 2 Signal is set using the parameter No. 23 “Zone Boundary 2 “+” Side” and No. 24 “Zone
Boundary 2 “–“ Side”.
The Zone 1 Signal and Zone 2 Signal become effective when the home return operation is completed. After
that, even during the servo OFF, it is effective.


[2] Position

zone

Each zone is set in the position table or using the zone boundary resister.
In the case of the Position/Simplified Direct Value Mode, the PZONE signal is set using the position table.
In the case of the Full Direct Value Mode, the PZONE signal is set using the Zone Boundary Value Register.
(*)In the Half Direct Value Mode, there is no PZONE signal.
The PZONE signal becomes effective with the movement command after the home return operation. After
that, even during the servo OFF, it is effective.













Zone setting – Zone setting +

+ direction

Actuator operation

Zone signal

Home

Advertising
This manual is related to the following products: