IAI America XSEL Ethernet User Manual

Page 27

Advertising
background image

- 21 -

4.4.2

Big Endian Operation

To align the word handling between Modbus/TCP and the X-SEL controller, the I/O operation mode
must be set to the big endian with an FMIO command before executing a DI/DO operation
command in any X-SEL task.
With this setting the remote I/O field accessed via word operation with an IN, INB, OUT or OUTB
command of the X-SEL controller can be handled as the same data when the same field is
word-accessed via Modbus/TCP.
The following examples are based on 256-bit assignments from the head DO number (= 300) in
X-SEL as Modbus/TCP remote I/Os.
The only difference from the examples shown in 4.4.1, “Little Endian Operation,” is the byte order
of the word registers.
(Note) Remote I/Os can be defined only as consecutive numbers.

The assignable head number must satisfy: 300 + 8n (31

 n  0).

The total number of assignable bits must satisfy: m + n < 32 & 32

 m, where m represents

the number of assigned remote I/O bytes.

[Modbus/TCP input areas (assignment of X-SEL DO area 300 onward)]

Address

BIT7

(MSB)

6 5 4 3 2 1

0

(LSB)

X-SEL

DO

307 306 305 304 303 302 301 300

Modbus/TCP

bit

address

0 1 2 3 4 5 6 7

Modbus/TCP word address

0 Upper byte

Modbus input status

10001

10002

10003

10004

10005

10006

10007

10008

Modbus input register

30001 Upper byte

X-SEL

DO

315 314 313 314 315 310 309 308

Modbus/TCP bit address

8

9

10

11

12

13

14

15

Modbus/TCP word address

0 Lower byte

Modbus input status

10009

10010

10011

10012

10013

10014

10015

10016

Modbus input register

30001 Lower byte

:

:

X-SEL

DO

547 546 545 544 543 542 541 540

Modbus/TCP

bit

address 240 241 242 243 244 245 246 247

Modbus/TCP word address

15 Upper byte

Modbus input status

10248

10249

10250

10251

10252

10253

10254

10255

Modbus input register

30016 Upper byte

X-SEL

DO

555 554 553 552 551 550 549 548

Modbus/TCP bit address

15 Lower byte

Modbus/TCP

word

address

248 249 250 251 252 253 254 255

Modbus input status

10249

10250

10251

10252

10253

10254

10255

10256

Modbus input register

30016 Lower byte

Cannot be used


Input status:

input discretes

single bit, provided by an I/O system, read-only

Output coil:

output discretes

single bit, alterable by an application program, read-write

Input register:

input registers

16-bit quantity, provided by an I/O system, read-only

Output register: output registers

16-bit quantity, alterable by an application program, read-write

The output areas are described on the next page.