13. Frequency
Analysis Function for SCON-CA
Controller
Anti-V
ibration Control
213
[3] Perform FFT analysis of the desired data to extract the vibration frequency of the load.
Fig. 13.4 Analysis Result Display Window
[4] Set the characteristic vibration frequency in the “Peak Freq [Hz]” field, and then select
Forward to
Controller and set the parameters.
Fig. 13.5 Analysis Result Display Window
FFT analysis
result
FFT analysis
result