ATRT-01 S2, ATRT-01B S2, AND ATRT-01D S2 USER’S MANUAL

REV 2

22

Type the X winding name plate voltage value using the numeric keypad. The
screen will be updated as shown:

Press the

[ENTER]

key. Continue to step d.

2. NO

Press the

[2]

key (NO) if you do not want to enter the transformer name plate

voltage. Continue to step d.

d. The following screen will be displayed:

Press the

[START]

key to start the test.

e. The following screen will be displayed while the test is being performed:

The test results will be displayed on the LCD screen when testing has finished:

The polarity is displayed as either a plus sign (+) for “in-phase” or a minus sign (-) for
“out-of-phase”. The value listed under “% DIFF” is the percentage error.

Press any key to continue.

SINGLE PHASE XFORMER

PLEASE WAIT

TEST IN PROGRESS

SINGLE PHASE XFORMER

“START” TO RUN TEST

OR

“STOP” TO ABORT

ENTER H WINDING
NAME-PLATE VOLTAGE:
10 V

ENTER X WINDING
NAME-PLATE VOLTAGE:
V