REV 2 ATRT-01 S2, ATRT-01B S2, AND ATRT-01D S2 USER’S MANUAL

25

Press the

[ENTER]

key. The following screen will be displayed:

Type the X winding name plate voltage value using the numeric keypad. The
screen will be updated as shown:

Press the

[ENTER]

key. Continue to step e.

2. NO

Press the

[2]

key (NO) if you do not want to enter the transformer name plate

voltage. Continue to step e.

e. The following screen will be displayed showing the Phase A cable connections for the

selected test (this will differ depending on the test):

Make the cable connections per the instructions and then press the

[START]

key to

run the Phase A test.

f. The following screen will be displayed while the test is being performed:

DYN 1 TRANSFORMER


PLEASE WAIT...

CABLE PHS-A XFMR
X1,X2 to X1,X0
H1,H2 to H1,H3

“START” TO RUN TEST

ENTER H WINDING
NAME-PLATE VOLTAGE:
10 V

ENTER X WINDING
NAME-PLATE VOLTAGE:
V

ENTER H WINDING
NAME-PLATE VOLTAGE:
500 V