REV 2 ATRT-01 S2, ATRT-01B S2, AND ATRT-01D S2 USER’S MANUAL

29

3.5.4. Performing a Single Phase Transformer Test Using Preset Voltage Table

The ATRT is pre-programmed with 46 transformer name plate voltages. These pre-programmed
values can be used to quickly test a single phase transformer’s turns ratio and compare the test
results against the name plate voltage. Please see Table 8 for a list of the pre-programmed
name plate voltages. Follow the steps below to perform a single phase transformer test using a
pre-programmed name plate voltage:

a. Start from the “START-UP” menu:

Press the

[CLEAR]

key.

b. The following screen will be displayed:

Press either the

[ Contrast]

key or the

[ Contrast]

key to scroll through the pre-

programmed name plate voltage values.

Continue to press the

[ Contrast]

key or the

[ Contrast]

key until the desired

name plate voltage values are displayed on the screen.

Press the

[START]

key when the desired name plate voltage values are displayed.

c. The following screen will be displayed while the test is being performed:

The test results will be displayed on the LCD screen when testing has finished (multiple
examples shown:

Example results from a passed test

Example results from a failed test

using nameplate voltages.

using nameplate voltages.

M-RATIO=+20.05

ERROR= 2.5 %

FAILED TTR TEST

2,400/120 R=20.00

M-RATIO=+20.05

ERROR= 0.25 %

PASSED TTR TEST

2,400/120 R=20.00

SINGLE PHASE XFORMER

PLEASE WAIT

TEST IN PROGRESS

SCROLL TO SELECT

“START” TO RUN TEST

H = 2,400
X = 120

1.TEST XFMR 06/02/10
2.SETUP 15:33:10
3.CALCULATOR