1 cable marking and identification, Cable marking and identification, Table 3.0 – Vanguard Tri-Phase User Manual
Page 15: Cable markings and identification

TRI-PHASE OPERATING™ INSTRUCTIONS
15
6.1
Cable Marking and Identification
Both the H and X cable test leads are terminated with heavy-duty battery clips. Test cable leads are
identified as follows.
Table 3.0
Cable Markings and Identification
Test Cable Name
Transformer Terminals Clip
Color
Identification
Single Phase H Cables
H1
Red
H1/1U/A
Single Phase H Cables
H2
Red
H2/1V/B
Single Phase X Cables
X1
Black
X1/2U/a
Single Phase X Cables
X2
Black
X2/2V/b
Three Phase H Cables
H0
Red
H0/1N/n
Three Phase H Cables
H1
Red
H1/1U/A
Three Phase H Cables
H2
Red
H2/1V/B
Three Phase H Cables
H3
Red
H3/1W/C
Three Phase X Cables
X0
Black
X0/2N/n
Three Phase X Cables
X1
Black
X1/2U/a
Three Phase X Cables
X2
Black
X2/2V/b
Three Phase X Cables
X3
Black
X3/2W/c
LTC Cable
RAISE (two connections)
Green
RAISE
LTC Cable
LOWER (two connections)
White
LOWER