Termination, Cable selection, Figure 7b multiple unit wiring – Warner Electric CBPC-3590 User Manual

Page 13: Figure 7a single unit wiring

Advertising
background image

Warner Electric • 800-825-9050

P-291-1 • 819-0526 13

Figure 7b Multiple Unit Wiring

Termination

The RS-422A/485 receivers require termination to
minimize the effects of noise while the bus is not
being driven. The CBPC-3590 incorporates the
terminations shown below internally. When
connection is made to a RS-422/485 device other
than the CBPC-3590, the receiver should be
terminated as shown.

Cable Selection

The CBPC-3590 serial interface uses a simple
interconnect scheme and low cost wiring mak-
ing it superior to parallel data transfer schemes .
Through two (2) wire shielded pairs, remote
operation at distances up to 5,000 feet can be
implemented. The following general guidelines
should be observed .

1. Use # 24 AWG twisted pair, overall shielded

cable .

2 . Use a “daisy chained” connection scheme for

bus systems .

3. If a “multidrop” system is used, keep the drop

length at 10% of the main line.

4. Tie the cable shield to the Building Ground at

the CBPC-3590 end of the cable.

RXD

COM

TXD

RS232 to

RS422/485

Converter

TXD+

TXD-

SHLD

RXD-

RXD+

6

5

4

3

2

1

CBPC-3590

Display/Keypad

Twisted Pairs with Shields

J4

Figure 7a Single Unit Wiring

TXD+

from

CBC-1000

TXD-

2

10 k Ω max. to

100 Ω min.

COM

to
receiver

+5V

RXD

COM

TXD

RS232 to

RS422/485

Converter

TXD+

TXD-

SHLD

RXD-

RXD+

6

5

4

3

2

1

J6

Keypad/Display

CBPC-3590

6

5

4

3

2

1

Keypad/Display

CBPC-3590

J4

} {

J4 Connections
Pin 6

TXD+

Pin 5

TXD-

Pin 4

RXD-

Pin 3

RXC+

Pin 2

Shield to Chassis End

Pin 1

Shield to Chassis En

d