HMI5000P Installation Guide

1010-1014 Rev 01 www.maplesystems.com

Maintenance

Figure 6: DIP switch positions (power must be cycled on the HMI to enable the DIP
switch mode).

SW1

SW2

SW3

SW4

Mode

ON

OFF

OFF

OFF

Calibration mode

OFF

ON

OFF

OFF

Hide System Toolbar

OFF

OFF

ON

OFF

Force into Boot Loader mode

OFF

OFF

OFF

ON

Reserved

OFF

OFF

OFF

OFF

Normal operation


Touchscreen Calibration mode: This mode allows you to recalibrate
the touchscreen.

Hide System Toolbar: Hides the arrow in the bottom-right corner of the
screen that accesses the System Toolbar (same as “Hide System Toolbar”
in System Parameters and LB9020).

Boot Loader mode: This mode forces the HMI to not execute the
project. This mode is used when replacing or reinstalling the operating
system. Contact Maple Systems for more information.

Fusing Requirements

If the display does not come on within two seconds of power up, remove
power. An internal fuse will prevent damage if the polarity of the DC
power is incorrect. Check wiring to insure proper connections and try to
power up again.