HMI5000P Installation Guide

1010-1014 Rev 01 www.maplesystems.com

Figure 2: Chassis Ground Connection

Power Supply Selection

The power supply used to power the HMI should provide an output of
+24 VDC ±20% measured at the HMI power terminal block. A 24VDC
regulated power supply dedicated to the HMI is recommended. Use a
power supply with adequate current rating based upon your particular
model (visit the Support Center Specifications page on our website).

A power line filter installed at the AC input to the HMI power supply is
highly recommended as a safeguard against conducted RF noise, which
is often present on factory power lines. The wires connecting the output
of the power line filter to the power supply should be kept as short as
possible to minimize any additional noise pickup. The case of the power
line filter should be connected to a quiet earth ground. The power line
filter should have a current rating of at least 3 Amps with common mode
and differential mode attenuation. In applications that may have high
frequency noise present, we also recommend using a resistor (~1 MΩ)
and capacitor (~4700 pF) in parallel to clean earth ground on the DC
output of the power supply.

Do not use the power supply used to provide power to the HMI to power
switching relays, solenoids, or other active devices.

Area on panel
free of paint

Stud or screw

Green (FG)

Red (+)

Black (--)

Control Panel
(connected to
earth ground)

Metal

Frame
ground