Proface GP4600R - 12.1 Standard HMIs with Rear Mounting Options" User Manual
Page 17
19
Installation
En
g
lish
•
When installing the GP unit in a slanted position, the GP unit face should
not incline more than 30°.
•
When installing the GP unit in a slanted position with an incline more than
30°, the ambient temperature must not exceed 40 °C (104 °F). You may
need to use forced air cooling (fan, A/C) to ensure the ambient operating
temperature is 40°C or less (104 °F or less).
•
For easier maintenance, operation and improved ventilation, install the GP
unit at least 100 mm (3.94 in.) away from adjacent structures and other
equipment as shown in the following illustration.
•
The holes on the rear of the GP unit are not correspondent with VESA 75mm
standards. Do not attach the GP unit to the commercial-type VESA arm.
R
RUOHVV
mm
in.
100
3.94
100
3.94
100
3.94
100 3.94
100 3.94
100 3.94
100 3.94