2 lt-3300 series, 2 lt-3300 series -11 – Proface LT3300 - 5.7 All-in-One HMI" User Manual

Page 26

Advertising
background image

Chapter 1 Overview

1-11

1.3.2

LT-3300 Series

A: Status LED
This LED indicates the LT’s status, e.g. power
input, firmware RUN status or backlight condition.

Also, indicates the status of logic program
execution.

B: DIO Interface (DIO)
This is the interface to mount external I/O

equipment using the DIO connector.
C: AUX Unit Interface/Expansion Unit (EXT2)
Interface where additional units such as
communication devices can be connected.
D: EX Module Interface (EXT1)
This is the interface to mount the Pro-face’s EX

module.
E: Power Plug Connector
F: Ethernet Interface
(10BASE-T/100BASE-TX)
The Ethernet transmission interface (10BASE-T/

100BASE-TX). An RJ-45 type modular jack
connector (8-pole) is used. The LED turns on or off
to indicate the current status.

G: USB Host Interface (USB)

Conforms to USB1.1. (TYPE-A conn.)
Power Supply Voltage: DC5V ± 5%
Output Current: 500mA (at maximum)

Connects a data transfer cable or USB-compatible
printer. The maximum communication distance is
5m.
H: Serial Interface (COM1)

RS232C/RS422/RS485 serial interface. D-sub 9-
pin plug type connector. Communication method is
switched via software.

Color

Indicator

Operation

Mode

(Drawing)

Logic execu-

tion mode

(when logic is

enabled)

Green

ON

OFFLINE

-

In

operation

RUN

Flashing

In

operation

STOP

Red

ON

When power is turned on.

Flashing

In

operation

Major Error

Orange

ON

Backlight burnout

Flashing

During software startup

LED

Indicates

Green ON

Data transmission available

Green OFF

No connection or subsequent

transmission failure

Yellow ON

Data transmission is

occurring.

Yellow OFF

No data transmission

Front

Back

A

Bottom

C

B

F

Right side

G

H

E

D

Advertising