Proface LT3300 - 5.7 All-in-One HMI" User Manual
Page 51

LT3000 Series Hardware Manual
2-24
Input Derating
Using LT input voltage that exceeds the rated voltage, the input ON voltage, the number of input points or the
LT’s temperature can effect. Also, the LT’s input section could overheat, which could lead to an accident or
malfunction. Refer to the following drawing and perform Input Derating within the LT unit’s rated range.
Input Points
16
Common Lines
1
Common Design
16 points/1 common line
Operation
Range
ON Voltage
DC19V or more
OFF Voltage
DC5V or less
Input Delay
Time
*1
OFF to ON
0.5 to 20ms
*2
ON to OFF
0.5 to 20ms
Input Signal Display
No LED indicators
Status Display
None
Isolation Method
Photocoupler Isolation
External Connection
38-pin connector (used with Output section)
External Power Supply
For Signal: DC 24V
*1
In the case of IN0, IN2, IN4, and IN6, the input delay time generates a 5µs-
delay. For example, in the case of a 0.5ms-cycle sampling:
5µs (ON to OFF) + 0.5ms (sampling cycle) + 5µs (OFF to ON) = 0.51ms
A minimum 0.51ms-restriction is imposed on the input pulse width.
In the case of IN1, IN3, IN5, and from IN7 to IN15, the input delay time gen-
erates a 0.5ms-delay. For example, in the case of a 0.5ms-cycle sampling:
0.5ms (ON to OFF) + 0.5ms (sampling cycle) + 0.5ms (OFF to ON) = 1.5ms
A minimum 1.5ms-restriction is imposed on the input-pulse width.
*2
Digital filter can be set at intervals of 0.5 ms.
(%)
100
50
0
0
10
20
30
40
50 (
°C)
Input ON Rate
Surrounding Operating Temperature
DC28.8V
For horizontal mounting
DC24.0 to 26.4V
For vertical mounting
DC24.0 to 25.2V