Watlow 12LS Controller User Manual

Page 108

Advertising
background image

G-3

Scaling Enter two values of unscaled process readings RDG

and their corresponding scaled process values PV.
Try to have as near as possible to zero and full
scale. Once entered the 8LS calculates linear
scaling from these values and scales all
subsequent measured data. This should be entered
prior to any other loop data.

Setpoint The desired control setting. This will be in

engineering units after scaling.

Spread For heat/cool dual output loops, this entry offsets

the heat and cool control points from the entered
setpoint. The heat will start to control when the
process is one half the spread below the setpoint.
The cool will start to control when the process is
one half the spread above the setpoint. When the
process is between the spread values there is no
control output.

TI Integral or Reset of the PID. The time constant is

in seconds.

TD Derivative or Rate of the PID. The time constant

is in seconds.

Units Three characters that will appear in the display

next to the process variable.