Watlow 12LS Controller User Manual

Page 50

Advertising
background image

4-17

4.5.1.8 COMMUNICATION ERROR CHECKING METHOD

This menu is used to select the checksum algorithm used in the ANAFAZE communications protocol. Either BCC
(block check character) or CRC (cyclic redundancy check) may be chosen.

|-----------------------------------------------------|
¦ NOTE: If using ANASOFT software to communicate to ¦
¦the controller make sure that the ANASOFT INSTALL ¦
¦program has been set for the same error checking ¦
¦ method. ¦
|-----------------------------------------------------|

The display will appear as :

|----------------|
¦ COMMUNICATIONS ¦
¦ ERR CHECK ? xxx¦
|----------------|

Press YES to select the menu or NO to advance to the next menu.

Press UP and DOWN to toggle the selection between CRC and BCC.

Press ENTER to store the error checking method or press BACK to return to the SETUP GLOBAL PARAMETERS
main menu prompt.

4.5.1.9 COMMUNICATION BAUD RATE

This menu is used to set the communications baud rate. Either 2400 or 9600 baud may be chosen. The controller
defaults to the higher rate of 9600.

|-----------------------------------------------------|
¦ NOTE: If using ANASOFT software to communicate to ¦
¦the controller make sure that the ANASOFT INSTALL ¦
¦program has been set for the same baud rate. ¦
|-----------------------------------------------------|

The display will appear as :

|----------------|
¦ COMMUNICATIONS ¦
¦BAUD RATE ? xxxx¦
|----------------|

Advertising