4-29

4.5.5.1 HIGH PROCESS ALARM SETPOINT

This menu is used to set the point within the scaled sensor range at which the high process alarm is activated. The
display appears as :
|----------------|
¦LL HI PROC ALARM¦
¦SETPOINT ? xxxx ¦
|----------------|

Press YES to select the menu or NO to advance to the next menu.

Press UP and DOWN to adjust the high process alarm setpoint.

Press ENTER to store the setpoint or press BACK to return to the SETUP LOOP ALARMS main menu prompt.

4.5.5.2 HIGH PROCESS ALARM STATUS

This menu is used to enable or disable the high process alarm. OFF disables the alarm function, ON enables it. The
display appears as:
|----------------|
¦LL HI PROC ALARM¦
¦ STATUS ? xxx ¦
|----------------|

Press YES to select the menu or NO to advance to the next menu.

Press UP and DOWN to toggle the selection between OFF and ON.

Press ENTER to store the alarm status or press BACK to return to the SETUP LOOP ALARMS main menu prompt.

4.5.5.3 HIGH PROCESS ALARM OUTPUT ASSIGNMENT

This menu is used to assign a digital output to be used by the high process alarm. Set to OFF to disable the output
function or 1-9 for the desired digital output number. The display appears as:
|----------------|
¦LL HI PROC ALARM¦
¦OUTPUT NR ? xx ¦
|----------------|

Press YES to select the menu or NO to advance to the next menu.

Press UP and DOWN to step through the available output numbers (1 through 9) or turn OFF the output function.

Press ENTER to store the output assignment or press BACK to return to the SETUP LOOP ALARMS main menu
prompt.