Watlow ANASCAN User Manual

Page 38

Advertising
background image

30 ANASCAN User’s Guide

CHANNEL SETUP

* The input types you can select depend on the type and options
installed in the CAS. The input types available are displayed in the input
type editing prompt. Input types available in the CAS:

Thermocouple: Various types are available. The range is deter-

mined in firmware and by the Engineering Units selected.

Linear: This is a linear voltage input type. it can be used with any

linear output sensor that can be scaled to the linear input voltage
range of the CAS.

Pulse: This allows devices which generate digital pulse signals such

as optical encoders to be connected to the channel.

The table below describes the input types and ranges.

Hi RDG

-99.9 to 999.9
Default = 1000

Linear and Pulse only,
Adjustable decimal

Lo RDG

-99.9 to 99.9
Default = 0

Input Type

°

F Range

°

C Range

J

-350 to 1400

-212 to 760

K

-450 to 2500

-268 to 1371

T

-450 to 750

-268 to 399

S

0 to 3200

-18 to 1760

R

0 to 3210

-18 to 1765

N

-450 to 2370

-268 to 1299

B

150 to 3200

66 to 1760

PL-II

+50 to 2012

+10 to 1100

Skip

channel is not scanned or displayed

Linear

See Appendix.

Pulse

0-2KHz

Field Name

Selections

Notes

Advertising