Example 2, Example 3 – Watlow ANASCAN User Manual

Page 60

Advertising
background image

52 ANASCAN User’s Guide

APPENDIX: Input Scaling

This table shows the input readings.

The scaling values are therefore:

Example 2

Situation

A flow sensor connected to the CAS measures the flow in a pipe. The
sensor generates a 0-5V signal. The sensor's output depends on its
installation. Independent calibration measurements of the flow in the
pipe indicate that the sensor generates 0.5 volts at three gallons per
minute (GPM) and 4.75 volts at 65 GPM. The calibration instruments
are precise to ±1 gallon per minute.

Setup

The sensor is connected to a channel input set up with a resistor voltage
divider network to produce 60 millivolts at 5 volts. (See the Inputs
section of the Installation chapter for information on scaling networks.)

The calibrating instrument is precise to ±1 gallon per minute, so the
appropriate display format is -999 to +3000.

This table shows the input readings.

The scaling values are therefore:

Example 3

Situation

PV

Displayed

Sensor Input

Reading (%FS)

50.0 psi

20

100%

0.0

4

100% x (4ma/20ma) = 20%

Parameter

Low Value

High Value

Process Value (PV)

0.0 psi

50.0 psi

Input Reading (RDG)

20.0

100.0

PV

Displayed

Sensor Input

Reading (%FS)

65 GPM

4.75

(4.75 V/ 5.00 V) x 100% = 95%

3 GPM

0.5

(0.5 V/ 5.00 V) x 100% = 10%

Parameter

Low Value

High Value

Process Value (PV)

3 GPM

65 GPM

Input Reading

10.0

95.0

Advertising