Alarm output data – Watlow ANASCAN User Manual
Page 39
CHANNEL SETUP
ANASCAN User’s Guide 31
Alarm Output Data
Field Name
Selections
Notes
High Process
Alarm
O = OFF (default)
No alarm
L = Latched
If the system is in a Non-Alarm-
ing state, the alarm can be
acknowledged by pressing the
ENTER key from the alarm
screen when the Process Alarm
indicator is flashing. Reset the
alarm by pressing F10 and enter-
ing each affected channel number
individually. This can also be
accomplished by pressing the
ALARM RESET button on the
CAS front panel.
U = Unlatched
Digital output activates on alarm,
and deactivates when channel is
in a Non-Alarming state. Press
ENTER to acknowledge the glo-
bal alarm.
High Process
Alarm Setpoint
-350 to 1400
default = 1000
Depends on input type selected.
High Process
Alarm Output
N, 1 to 34
default = NONE
N = NONE
Low Process
Alarm
O = OFF(Default)
L = Latched
U = Unlatched
See above descriptions.
Low Process
Alarm Setpoint
-350 to 1400
default = 0
Depends on input type selected.
Low Process
Alarm Output
N, 1 to 34
default = NONE
N = NONE