Setup – Watlow Series 945, 1/4 DIN Microprocessor-BasedAuto-tuning Control User Manual

Page 16

Advertising
background image

Setup, Chapter 4

16

WATLOW Series 945 User's Manual

Setup

AL1

Alarm 1: Determines whether the alarm type for Alarm 1 is process, deviation, or
none. A process alarm is set at an absolute temperature. A deviation alarm follows
or tracks the set point. This parameter only appears if your unit has alarms.
Range: Pr, dE, no Default: Pr

Latching 1: Selects whether Alarm 1 is latching or non-latching. Latching alarms
must be cleared before the alarm output will reset. Non-latching automatically resets
the alarm output when the condition clears. This parameter will not appear if AL 1 =
no, or your unit does not have alarms. Range: LAt or nLA Default: nLA

Hysteresis 3: Selects the switching hysteresis for Alarm 1. Appears if
your unit has alarms and AL 1 = Pr or dE.
Range:

1°F - 99°F

0.1°F - 9.9°F

Default: 3°F

1°C - 55°C

0.1°C - 5.5°C

1 Unit - 99 Units

0.1 Unit - 9.9 Units

Output 4: Selects Output 4 as retransmit of Process (PrOC) or Set Point (StPt).
Hardware must be present. Scaling of the retransmit output is determined by rL and
rH.

Range: PrOC, StPt, no

Default: PrOC

Alarm 2: Determines whether Alarm 2 type is process, deviation, or none. A process
alarm is set at an absolute temperature. A deviation alarm follows or tracks the set
point. This only appears if your unit has alarms.
Range: Pr, dE, no

Default: Pr

Latching 2: Selects whether Alarm 2 is latching or non-latching. Latching alarms
must be cleared before the alarm output will reset. Non-latching automatically resets
the alarm output when the condition clears. Will not appear if your unit does not have
alarms or AL2 = no. Range: LAt or nLA Default: nLA

Hysteresis 4: Selects the switching hysteresis for Alarm 2. Appears if
your unit has alarms and AL 2 = Pr or dE.
Range:

1°F - 99°F

0.1°F - 9.9°F

Default: 3°F

1°C - 55°C

0.1°C - 5.5°C

1 Unit - 99 Units

0.1 Unit - 9.9 Units

Silencing: Selects alarm silencing (inhibit) for Alarm 1. This parameter only appears
when AL1 = dE. For more information see Chapter 5.
Range: On or OFF

Default: OFF

RTD: Selects the RTD calibration curve for RTD inputs. Appears if In = rtd or rt.d.
JIS = 0.003916

/

°C, DIN = 0.003850

/

°C.

Range: din or JIS

Default: din

Any parameters that appear after RTD are related to data communications. See

How

to Use Data Communications with the Watlow Series 945 for more information.

LAt1

HYS3

Ot4

AL2

LAt2

HYS4

SIL

rtd

Input Type

Sensor Range Low

Sensor Range High

J

32°F/0°C

1382°F/750°C

K (appears as H)

-328°F/-200°C

2282°F/1250°C

t

-328°F/-200°C

662°F/350°C

n

32°F/0°C

2282°F/1250°C

c

797°F/425°C

4200°F/2315°C

Pt2

32°F/0°C

2543°F/1395°C

r

32°F/0°C

2642°F/1450°C

S

32°F/0°C

2642°F/1450°C

b

1598°F/870°C

3092°F/1700°C

rtd (1°)

-328°F/-200°C

1112°F/600°C

rt.d (0.1°)

-99.9°F/-99.9°C

392.0°F/200.0°C

0-5 (VDC)

-5.00/-50.0/-500

35.00/350.0/3500

420 (mA)

-5.00/-50.0/-500

35.00/350.0/3500

Table 1 -
Input Ranges.