Output 1 wiring – Watlow Series 945, 1/4 DIN Microprocessor-BasedAuto-tuning Control User Manual

Page 7

Advertising
background image

Install and Wire, Chapter 2

7

WATLOW Series 945 User's Manual

Output 1 - Solid State Relay With Contact Suppression

Output 1 Wiring

Mechanical Relay, Form C, 6 Amp

17

16

18

N.O.

COM.

External

Load

Fuse

L1

L2

N.C.

Off state impedance: 20K

min.

17

16

Switched DC, Open Collector,

Non-Isolated

Logic

Switch

External

Load

+

-

+

-

Output 1 - Switched DC Output (Open Collector)

Output 1 - Process, 4 - 20mA

Output 1 - Mechanical Relay, 6 Amp, Form C

945A - _

B

_ _ - _ 000

945A - _

C

_ _ - _ 000

945A - _

D

_ _ - _ 000

Figure 12 -
Switched DC
(Open Collector)

Figure 13 -
6 Amp Mechanical
Relay

NOTE:
Minimum load
resistance is 500 .
Available current is
22mA maximum.
Typical voltage drop
across a 1K load is
12 to 19 volts.

Figure 11 -
Solid State Relay
With Contact
Suppression

NOTE:
This output is
supplied with an arc
suppression snubber
across the output
terminals. High
impedance loads may
remain energized
even though the
output device is
turned OFF.

N.O.

COM.

External

Load

Fuse

L1

L2

18

17

Off state impedance: 31M

max.

Suppression

Off state impedance: 20K max.

18

17

Process, 4-20 mA, Non-Isolated

External

Load

-

+

I

DC

+

-

Load impedance: 600

max.

945A - _

F

_ _ - _ 000

Figure 14 -
Process, 4-20mA

Advertising