20 operation menu table, Operation, Operation menu – Watlow Series 945, 1/4 DIN Microprocessor-BasedAuto-tuning Control User Manual

Page 20

Advertising
background image

Setup, Chapter 4

20

WATLOW Series 945 User's Manual

Operation

Operation Menu

Use this page as a master copy for your Series 945 Operation parameters.
Do not enter any values here; make photocopies instead.

Table 3 -
Operation Menu
Prompts and
Descriptions.

Parameters

Value

Range

Factory Default

Appears If:

Set Point 1 or

rL to rH

75°F

Remote Set Point 1

SP2

rL to rH

Primary set point.

Ot1 = Ot2, Pb1 = 0

Pb1

If dFL = US:
0 - 999°F/0 - 555°C/0 - 999U

25°F/2.5°F

0 - 99.9°F/0 - 55.5°C/0 - 99.9U
0=ON/OFF control. HYS1 =swtch. diff.
If dFL = SI:
0 to 999.9% of span

3%/.3%

Pb2

Same as Pb1.

0°F

Ot2 = ht or CL
Ot2

Ot1

rE1/It1

If dFL = US: 0.00 to 9.99 repeats/min.

0.00 rpt/min.

Pb1

0

0.00 = No Reset.
If dFL = SI: 00.1 to 99.9 min./repeat

0.00

rE2/It2

Same as rE1/It1.

0.00 rpt/min.

Pb2

0, Ot2

Ot1

Ot2 = ht or CL

rA1/dE1

0.00 to 9.99 min.

0.00 min.

Pb1

0

0.00 = No Rate.

rA2/dE2

Same as rA1/dE1.

0.00 min.

Pb2

0, Ot2

Ot1

Ot2 = ht or CL

Ct1

1 to 60 seconds

5 seconds

Pb1

0, Output1

420

Ct2

1 to 60 seconds

5 seconds

Pb2

0, Ot2

Ot1,

Ot2 = ht or CL

db

±0 - 99°F/±0 - 55°C/0 - 99U.

0

Ht/CL or CL/Ht

±0.0 - 9.9°F/0.0 - 5.5°C/0.0 - 9.9U

A1LO Deviation dE

-999° to 0°

-999°

AL1 = Pr, dE

Process Pr

rL to A1HI

rL

Unit has alarms

A1HI

Deviation dE

0° to 999°

999°

AL1 = Pr, dE

Process Pr

A1LO to rH

rH

Unit has alarms

A2LO Deviation dE

-999° to 0°

-999

AL2 = Pr, dE

Process Pr

rL to A2HI

rL

Unit has Alarm 2

A2HI

Deviation dE

0° to 999°

999°

AL2 = Pr, dE

Process Pr

A2LO to rH

rH

Unit has Alarm 2

CAL

±180°F/±100°C/±180U

0

AUt

0-3

0

Ot1 = ht, L-r = L

L-r

L or r

L

rsP = 0-5 or 420

Auto-Tune: Initiates auto-tune for Output 1. This parameter appears if Ot 1 =ht.
Range: 0 = off, 1 = slow, 2 = medium, 3 = fast

Default: 0

Local-Remote: Selects a local or remote set point for the Series 945. This parameter
only appears if the LOC parameter = 0, 1 or 2, and rSP = 0-5 or 420. If L-r = r, the
remote set point will be displayed in place of the internal set point.
Range: L = Local operation r = remote operation

Default: L

AUt

L-r