17 setup menu table, Setup, Setup menu – Watlow Series 945, 1/4 DIN Microprocessor-BasedAuto-tuning Control User Manual

Page 17

Advertising
background image

Setup, Chapter 4

17

WATLOW Series 945 User's Manual

Setup

Setup Menu

Use this page as a master copy for configuring your Series 945.
Do not enter any values here; make photocopies instead.

Table 2 -
Setup Menu Prompts
and Descriptions.

Parameter

Value

Range

Factory Default

Appears If:

LOC

0 - 3

0

In

J, K (appears as H), t, n, c, Pt2,

J or r

r, S, b, rtd, rt.d, 0-5, 420

rSP

OFF, 0-5, 420

OFF

In = T/C or RTD

dEC

0, 0.0, or 0.00

0

In = 0-5 or 420

C _ F

C or F

F

In = T/C or RTD

rL

rL to rH

Input dependent.

rH

rH to rL

Input dependent.

Ot1

ht or CL

ht

HYS1

1°F - 99°F, 1°C - 55°C, 1U - 99U

3°F

0.1°F - 9.9°F, 0.1°C - 5.5°C, 0.1U - 9.9U

Ot2

ht, CL or no

CL

Unit has secondary output

HYS2

1°F - 99°F, 1°C - 55°C, 1U - 99U

3°F

Unit has secondary output

0.1°F - 9.9°F, 0.1°C - 5.5°C, 0.1U - 9.9U

Ot2 = ht or CL

AL1

Pr, dE or no

Pr

Unit has alarms

LAt 1

LAt or nLA

nLA

Unit has alarms and
AL1 = Pr or dE

HYS3

1°F - 99°F, 1°C - 55°C, 1U - 99U

3°F

Unit has alarms and

0.1°F - 9.9°F, 0.1°C - 5.5°C, 0.1U - 9.9U

AL1 = Pr or dE

Ot4

no, PrOC, StPt

PrOC

Hardware is present

AL 2

Pr, dE or no

Pr

Unit has alarms

LAt 2

LAt or nLA

nLA

Unit has alarms and
AL2 = Pr or dE

HYS4

1°F - 99°F, 1°C - 55°C, 1U - 99U

3°F

Unit has alarms and

0.1°F - 9.9°F, 0.1°C - 5.5°C, 0.1U - 9.9U

AL2 = Pr or dE

SIL

On or OFF

OFF

Unit has alarms & AL1 = dE

rtd

JIS or din

din

In = rtd or rt.d

Advertising