Appendix

34

WATLOW Series 945 User's Manual

Calibration

Calibration Menu

Figure 41 -
Calibration Menu

CAL

tCL

tCH

tC

rLO

rHI

O U

5 U

4 A

20A

4tYP

O4LO

O4HI

O1LO

O1HI

rst

dISP

dFL

MEM

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

( )

No

Yes

Before attempting to calibrate,

make sure you have the proper

equipment called for in each procedure.

The Series 945 is calibrated and tested

before leaving the factory.

Input 0.00mV for low thermocouple input.

Input 50.00mV (16.035 for r, S or b units) for high thermocouple input.

Connect a "J" T/C compensator, with inputs shorted. T/C units only.

Connect the JIS RTD low resistance per model number.

Connect the JIS RTD high resistance per model number.

Set the voltage source to 0.000 volts.

Set the voltage source to 5.000 volts.

Set the current source to 4.00mA.

Set the current source to 20.00mA.

Press the UP/DOWN keys until Output 1 reads process low.

Press the UP/DOWN keys until Output 1 reads process high.

Factory select for Output 4 type.

Press the UP/DOWN keys until Output 4 reads process low.

Press the UP/DOWN keys until Output 4 reads process high.

Restores factory calibration values.

Factory use only.

Select US (rate, reset, proportional band in degrees or units,

°

F) or SI

(integral, derivative, proportional band in % of span,

°

C).

Factory use only.

YES to calibrate, No skips to display test.