Restore, Default, Rst] [`dfl – Watlow Series 998 User Manual
Page 101: Factory-calibration
Advertising

WATLOW Series 998 User’s Manual
6.15
Factory Menus, Chapter 6
Factory-Calibration
Restore
Restores the original factory calibration values. This is a simple way to
recover if you make a mistake calibrating the controller.
[`rSt] This prompt always appears.
Default
↓
[``no]
[`yes]
[`rSt]
[`rSt]
Default
Set the operating parameter defaults to U.S. or international mea-
sures.
• [``US] (U.S.) sets the controller to °F; rate in minutes; proportional band
in degrees or units; and reset in repeats per minute.
• [``SI] (international) sets the controller to °C; derivative in minutes;
proportional band in percent of span; and integral in minutes per repeat.
[`dFL] This prompt always appears.
Default
↓
[``US]
[``sI]
[`dFL]
[`dFL]
[`rst]
[`dFL]
Advertising