Protocol type, Address, Interface type – Watlow Series 998 User Manual
Page 68: Addr] [intf] [prot, Setup-communications

4.40
WATLOW Series 998 User’s Manual
Setup Menus, Chapter 4
Setup-Communications
Protocol Type
Select the communications protocol.
• [FULL] selects ANSI X3.28 2.2 - A.3.
• [``on] selects XON/XOFF.
[Prot] This prompt appears only on controllers equipped with communi-
cations hardware (99__-____-_R__ or 99__-____-_S__).
Default
↓
[FULL]
[``On]
[Prot]
[Prot]
Address
Select an address for the controller. The computer will use this address
when communicating with this controller.
[Addr] This prompt appears only on controllers equipped with communica-
tions hardware for EIA/TIA-485 and EIA/TIA-422 (99__-____-_S__).
If
Default
↓
↓
[`485]
[```0]
…
[``31]
[IntF]
[Addr]
[Addr]
[`422]
[```0]
…
[```9]
[Intf]
[Addr]
[Addr]
Interface Type
Select the interface type.
• [`485] selects EIA/TIA-485.
• [`422] selects EIA/TIA-422.
[IntF] This prompt appears only on controllers equipped with communi-
cations hardware for EIA/TIA-485 and EIA/TIA-422 (99__-____-_S__).
Default
↓
[`485]
[`422]
[IntF]
[IntF]
[Addr]
[IntF]
[Prot]