Calibration offset 2, Rtd calibration curve 2, Cal2] [rtd2 – Watlow Series 998 User Manual
Page 41: Setup-input

WATLOW Series 998 User’s Manual
4.13
Setup Menus, Chapter 4
Calibration Offset 2
Offset the channel B signal by a positive or negative value. This allows
you to compensate for lead resistance, sensor errors or other factors.
[CAL2] This prompt appears only if [`In2] is not set to [``no].
If
Default
↓
↓
[``°F]
[-999]
…
[```0]
…
[`999]
[`C_F]
[CAL2]
[CAL2]
[CAL2]
(Global Menu)
[``°F]
&
[`r†d]
[-9(9]
…
[``)0]
…
[`9(9]
[`C_F]
[`In2]
[CAL2]
[CAL2]
[CAL2]
(Global Menu)
(Input Menu)
[``°C]
[-555]
…
[```0]
…
[`555]
[`C_F]
[CAL2]
[CAL2]
[CAL2]
(Global Menu)
[``°C]
&
[`r†d]
[-5%5]
…
[``)0]
…
[`5%5]
[`C_F]
[`In2]
[CAL2]
[CAL2]
[CAL2]
(Global Menu)
(Input Menu)
[-999]
…
[```0]
…
[`999]
units
a process input
[CAL2]
[CAL2]
[CAL2]
is selected
RTD Calibration Curve 2
Select the calibration curve for the channel B RTD 2 input. The RTD
input uses either the European (DIN, 0.003850
Ω
/
Ω
/°C) or the Japanese
(JIS, 0.003916
Ω
/
Ω
/°C) linearization standard.
[rtd2] This prompt appears only if you have set [`In2] to [`rtd] or
[`r†d].
Default
↓
[`din]
[`JIS]
[rtd2]
[rtd2]
Setup-Input
[CAL2]
[rtd2]