Watlow Series PD User Manual

Page 174

Advertising
background image

Name and Description

Web Page

Range (Scaling)

Iterations

Default

EIP Decimal (Hex)

Modbus

EIP Data Type

Access

High Current Scale
Set the input process current (in milliamps) that will
correspond to the High Process Scale.

Analog Input {1 or 2}

Configuration

0 to 20,000 (/1000)

Analog Input 1
Analog Input 2

20000

102/1/5 (66/1/5)
102/2/5 (66/2/5)

256-257
286-287

DINT

R/W

Temperature Process Value Units
Indicates the temperature units displayed in the
web pages for a thermocouple and RTD input.
This can be set in the web page.

Analog Input {1 or 2}

Configuration

Fahrenheit (0)

Celsius (1)

Analog Input 1
Analog Input 2

Fahrenheit (0)

108/1/35 (6C/1/23)
108/1/39 (6C/1/27)

1109
1120

UINT

R

Temperature Process Value Precision
Indicates the number of decimal places displayed
in the web pages for a thermocouple or RTD input.
This can be set in the web page.

Analog Input {1 or 2}

Configuration

0 (0)

0.0 (1)

Analog Input 1
Analog Input 2

0 (0)

108/1/33 (6C/1/21)
108/1/37 (6C/1/25)

1107
1118

UINT

R

Filter Method
Select a filter method to smooth out a rapidly
changing input signal.

Analog Input {1 or 2}

Configuration

Off (0)

First Order (1)

Analog Input 1
Analog Input 2

Off (0)

102/1/11 (66/1/B)
102/2/11 (66/2/B)

268
298

UINT

R/W

Filter Time Base
Set the filter time. A higher value will smooth out
the signal more.

Analog Input {1 or 2}

Configuration

100 to 60,000 (/1000)

Analog Input 1
Analog Input 2

100

102/1/12 (66/1/C)
102/2/12 (66/2/C)

269-270

DINT

R/W

Single Offset Value
Set a value to compensate for the input's lead
resistance and sensor inaccuracy.

Analog Input {1 or 2}

Configuration

-9,999,000 to 9,999,000

(/1000)

Analog Input 1
Analog Input 2

0

102/1/10 (66/1/A)
102/2/10 (66/2/A)

266-267
296-297

DINT

R/W

Device Configuration > Inputs > CT Input {3 or 4}
Function
Set whether to enable the CT input.

CT Input {3 or 4}

Configuration

Off (0)

CT Current (6)

CT Input 3
CT Input 4

Off (0)

102/3/1 (66/3/1)
102/4/1 (66/4/1)

311
331

UINT

R/W

CT Precision
Indicates the number of decimal places displayed
in the web page for CT inputs. This can be set in
the web page.

CT Input {3 or 4}

Configuration

0 (0)

0.0 (1)

0.00 (2)

0.000 (3)

CT Input 3
CT Input 4

0 (0)

108/1/42 (6C/1/2A)
108/1/46 (6C/1/2E)

1124
1128

UINT

R

CT Units
Indicates the units displayed in the web page for
CT inputs. This can be set in the web page

CT Input {3 or 4}

Configuration

Up to four alphanumeric

characters

CT Input 3
CT Input 4

108/1/44 (6C/1/2C)

108/1/48 (6C/1/30)

1125-1126
1129-1130

SHORT_STRING

R

Low CT Scale
Set the value that will be displayed when the
current transformer (CT) input is at its minimum,
as determined by the Low Current Scale.

CT Input {3 or 4}

Configuration

-30,000,000 to 30,000,000

(/1000)

CT Input 3
CT Input 4

-30,000,000

102/3/8 (66/3/8)
102/4/8 (66/4/8)

316-317
336-337

DINT

R/W

High CT Scale
Set the value that will be displayed when the
current transformer (CT) input is at its maximum,
as determined by the High Current Scale.

CT Input {3 or 4}

Configuration

-30,000,000 to 30,000,000

(/1000)

CT Input 3
CT Input 4

30,000,000

102/3/9 (66/3/9)
102/4/9 (66/4/9)

318-319
338-339

DINT

R/W

Low Current Scale
Set the input process current (in milliamps) that will
correspond to the Low CT Scale.

CT Input {3 or 4}

Configuration

0 to 50,000 (/1000)

CT Input 3
CT Input 4

0

102/3/4 (66/3/4)
102/4/4 (66/4/4)

312-313
332-333

DINT

R/W

High Current Scale
Set the input process current (in milliamps) that will
correspond to the High CT Scale.

CT Input {3 or 4}

Configuration

0 to 50,000 (/1000)

CT Input 3
CT Input 4

20,000

102/3/5 (66/3/5)
102/4/5 (66/4/5)

314-315
334-335

DINT

R/W

Output
Select output to monitor with the CT input.

CT Input {3 or 4}

Configuration

Output 1 (0)
Output 2 (1)
Output 3 (2)
Output 4 (3)

CT Input 3
CT Input 4

Output 2 (1)

102/3/13 (66/3/D)
102/4/13 (66/4/D)

322
342

UINT

R/W

Single Offset Value
Set a value to compensate for the input's lead
resistance and signal inaccuracy.

CT Input {3 or 4}

Configuration

-9,999,000 to 9,999,000

(/1000)

CT Input 3
CT Input 4

0

102/3/10 (66/3/A)
102/4/10 (66/4/A)

320-321
340-341

DINT

R/W

SERIES PD with EtherNet/IP

Addressing Information (rev c) 172

Advertising