W a t l o w S e r i e s P D

61

C h a p t e r 8 C a l i b r a t i o n P a g e

Calibrate Analog Output x (1 or 3)

To reach the Calibration web page, go to Device Configuration > Calibration. The Enter Network Password

box appears and you are prompted to enter Network Password information. The default User Name is new and
Password is user.

1. Select Calibrate Analog Output x
2. Select Low Volts
3. Click on Apply Signal
4. Measure actual output signal to 3 decimal places at appropriate output terminals and enter value in box.
5. Click on Calibrate
6. Select Go Back To Calibration Page
7. Select High Volts
8. Repeat steps 3 through 6
9. Select Low Milliamps
10. Repeat steps 3 through 6
11. Select High Milliamps
12. Repeat steps 3 through 6
13. Select Go Back To Calibration Page.
14. Verify calibration and rewire for operation.