<7. Operation>

7-7

IM 01C25K01-01E

[Example]
Rerange LRV to 0 and URV to 3 MPa.
1) Connect the transmitter and apparatus as

shown in Figure 8.1 and warm it up for at least

five minutes.

2) Press the range-setting push-button.

The integral indicator then displays “LRV.SET.”

3) Apply a pressure of 0 kPa (atmospheric

pressure) to the transmitter.

(Note 1)

4) Turn the external zero-adjustment screw in the

desired direction. The integral indicator displays

the output signal in %.

(Note 2)

5) Adjust the output signal to 0% (1 V DC) by

rotating the external zero-adjustment screw.

Doing so completes the LRV setting.

6) Press the range-setting push-button. The

integral indicator then displays “URV.SET.”

7) Apply a pressure of 3 MPa to the

transmitter.

(Note 1)

8) Turn the external zero-adjustment screw in the

desired direction. The integral indicator displays

the output signal in %.

(Note 2)

9) Adjust the output signal to 100% (5 V DC) by

rotating the external zero-adjustment screw.

Doing so completes the URV setting.

10) Press the range-setting push-button. The

transmitter then switches back to the normal

operation mode with the measurement range of

0 to 3 MPa.

Note 1: Wait until the pressure inside the pressure-detector

section has stabilized before proceeding to the next step.

Note 2: If the pressure applied to the transmitter exceeds the

previous LRV (or URV), the integral indicator may display

error number “AL.30” (In this case, the output signal

percent and “AL.30” are displayed alternately every two

seconds). Although “AL.30” is displayed, you may proceed

to the next step. However, should any other error number

be displayed, take the appropriate measure in reference

to , “Errors and Countermeasures” in each communication

manual.

IMPORTANT

• Do not turn off the power to the transmitter

immediately after completion of the change

in the LRV and/or URV setting(s). Note

that powering off within thirty seconds after

setting will cause a return to the previous

settings.

• Changing LRV automatically changes URV

to the following value.

URV=previous URV+(new LRV–previous LRV)
• If the range-setting push-button and external

zero-adjustment screw are not touched

during a range-change operation, the

transmitter automatically switches back to

the normal operation mode.

F0710.ai

Integral indicator

Range-setting switch

(Push-button)

Note 1: Use a thin bar which has a

blunt tip, e.g., a hexagonal

wrench, to press the

range-setting push-button.

Note 2: The push-button is located

in either lower right or

lower left portion of the

LCD indicator.

Figure 7.7

Range-setting Switch