<8. Maintenance>

8-2

IM 01C25K01-01E

Table 8.1

Instruments Required for Calibration

Name

Yokogawa-recommended Instrument

Remarks

Power supply Model SDBT or SDBS distributor

4 to 20 mA DC signal

Load resistor

Model 2792 standard resistor [250 Ω ±0.005%, 3 W]
Load adjustment resistor [100 Ω ±1%, 1 W]

Voltmeter

Model 2501 A digital multimeter

Accuracy (10V DC range): ±(0.002% of rdg + 1 dgt)

Digital

manometer

Model MT220 precision digital manometer

1) For 10 kPa class

Accuracy: ±(0.015% of rdg + 0.015% of F.S.). . . . for 0 to 10 kPa

±(0.2% of rdg + 0.1% of F.S.). . . . . . . . for -10 to 0 kPa

2) For 130 kPa class

Accuracy: ±0.02% of rdg. . . . . . . . . . . . . . . . . . . . for 25 to 130 kPa

±5digits. . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 25 kPa

±(0.2% of rdg + 0.1% of F.S.). . . . . . . . for -80 to 0 kPa

3) For 700 kPa class

Accuracy: ±(0.02% of rdg + 3digits) . . . . . . . . . . . for 100 to 700 kPa

±5 digits . . . . . . . . . . . . . . . . . . . . . . . . for 0 to 100 kPa

±(0.2% of rdg + 0.1% of F.S.). . . . . . . . for -80 to 0 kPa

4) For 3000 kPa class

Accuracy: ±(0.02% of rdg + 10 digits). . . . . . . . . . for 0 to 3000 kPa

±(0.2% of rdg + 0.1% of F.S.). . . . . . . . for -80 to 0 kPa

5) For 130 kPa abs class

Accuracy: ±(0.03% of rdg + 6 digits) . . . . . . . . . . . for 0 to 130 kPa abs

Select a manometer having

a pressure range close to

that of the transmitter.

Pressure

generator

Model 7674 pneumatic pressure standard for 200 kPa {2 kgf/cm

2

}, 25 kPa

{2500 mmH

2

O}

Accuracy: ±0.05% of F.S.

Requires air pressure

supply.

Dead weight gauge tester 25 kPa {2500 mmH

2

O}

Accuracy: ±0.03% of setting

Select the one having a

pressure range close to that

of the transmitter.

Pressure

source

Model 6919 pressure regulator (pressure pump)

Pressure range: 0 to 133 kPa {1000 mmHg}

Prepare the vacuum pump

for negative pressure

ranges.

Note: The above table contains the instruments capable of performing calibration to the 0.2% level. Since special maintenance and

management procedures involving traceability of each instrument to higher-level standards are required for calibration to the 0.1%

or higher level, there may be difficulties in calibration to this level in the field. For calibration to the 0.1% level, contact Yokogawa

representatives from which the instrument was purchased or the nearest Yokogawa office.

V

R

Rc

P

Using pressure

generator

Reference pressure

High pressure side

High pressure side

Low pressure side

open to atmosphere

Low pressure side

open to atmosphere

Supply pressure

Pressure generator

Load resistance,

250Ω

Load

adjusting

resistance,

100Ω

Digital voltmeter

Power

supply

E

V

R

Rc

P

Using pressure

source with

manometer

Reference pressure

Pressure source

Model MT220

precision digital manometer

Load resistance,

250Ω

Load

adjusting

resistance,

100Ω

Digital voltmeter

Power

supply

E

F0801.ai

Figure 8.1

Instrument Connections (EJX110A)