<8. Maintenance>

8-4

IM 01C25K01-01E

8.4.2 Replacing the CPU Board Assembly

This subsection describes the procedure for

replacing the CPU assembly. (See figure 8.3)

■ Removing the CPU Assembly
1) Remove the cover. If an integral indicator is

mounted, refer to subsection 8.4.1 and remove

the indicator.

2) Turn the zero-adjustment screw to the position

(where the screw head slot is horizontal) as

shown in figure 8.3.

3) Disconnect the output terminal cable (cable

with brown connector at the end). When doing

this, lightly press the side of the CPU assembly

connector and pull the cable connector to

disengage.

4) Use a socket driver (width across flats, 5.5mm)

to loosen the two bosses.

5) Carefully pull the CPU assembly straight

forward to remove it.

6) Disconnect the flat cable (cable with white

connector at the end) that connects the CPU

assembly and the capsule.

NOTE

Be careful not to apply excessive force to the

CPU assembly when removing it.

■ Mounting the CPU Assembly
1) Connect the flat cable (with white connector)

between the CPU assembly and the capsule.

2) Connect the output terminal cable (with brown

connector).

NOTE

Make certain that the cables do not get pinched

between the case and the edge of the CPU

assembly.

3) Align and engage the zero-adjustment screw

pin with the groove on the bracket on the CPU

assembly. Then insert the CPU board assembly

straight onto the post in the amplifier case.

4) Tighten the two bosses. If the transmitter is

equipped with an integral indicator, refer to

subsection 8.4.1 to mount the indicator.

NOTE

Confirm that the zero-adjustment screw pin is

placed properly in the groove on the bracket prior

to tightening the two bosses. If it is not, the zero-

adjustment mechanism will be damaged.

5) Replace the cover.

8.4.3 Replacing the Process Connector

Gaskets

This subsection describes process connector

gasket replacement. (See Figure 8.4.)
(a) Loosen the two bolts, and remove the process

connectors.

(b) Replace the process connector gaskets.

(c) Remount the process connectors. Tighten the

bolts securely and uniformly with a torque of 39

to 49 N·m {4 to 5 kgf·m}, and verify that there

are no pressure leaks.

F0804.ai

Process connector

Process connector gasket

Bolt

Figure 8.4

Removing and Mounting the Process

Connector

8.4.4 Cleaning Manifold Assembly and

Replacing Orifice

This subsection describes the procedures for

cleaning the manifold assembly and replacing the

orifice to change flow rate. (See Figure 8.5.)

■ Removing the Manifold Assembly
1) Remove the process connector as shown in

Subsection 9.4.3.

2) Remove the four bolts that connect the cover

flange with the manifold.

3) Remove the spacer, orifice, and orifice gasket

from inside the manifold.

4) Clean the manifold, spacer, and orifice, or

replace them as necessary.