<8. Maintenance>

8-7

IM 01C25K01-01E

Abnormalities appear in measurement.

: Areas where self-diagnostic offers support

Is process variable

itself abnormal?

Inspect the

process system.

Isolate problem in

measurement system.

Does problem exist in

receiving instrument?

Check/correct

environmental conditions.

Inspect receiver.

Check transmitter.

Check/correct operating

conditions.

Measurement system problem

F0807.ai

YES

NO

NO

YES

Environmental conditions

Operating conditions

Transmitter itself

Figure 8.7 Basic Flow and Self-Diagnostics

8.5.2 Troubleshooting Flowcharts

Connect communicator and check self-diagnostics.

Does the self-diagnostic

indicate problem location?

Contact Yokogawa service personnel.

F0808.ai

The following sorts of symptoms indicate that transmitter

may not be operating properly.

Example : • There is no output signal.

• Output signal does not change even though

process variable is known to be varying.

• Output value is inconsistent with value

inferred for process variable.

Is power supply

polarity correct?

Are power

supply voltage and load

resistance correct?

Refer to Section 6.3 to check/correct

polarity at each terminal from power

supply to the terminal box.

Fix pressure leaks, paying particular

attention to connections for impulse

piping,pressure-detector section, etc.

Fully close equalizing valve, and fully

open high pressure and low pressure

valves.

Refer to Section 6.6 for rated voltage

and load resistance.

Find/correct broken conductor or

wiring error.

Are valves opened or

closed correctly?

Is there any pressure leak?

Is there

continuity through the

transmitter loop wiring?

Do the loop numbers

match?

YES

NO

YES

NO

NO

YES

NO

NO

YES

YES

NO

YES

Refer to error message summary in

Subsection 8.5.3 or in each

communication manual to take actions.

Is orifice clogged with

dust, etc?

YES

NO

Refer to Subsection 8.4.4 to clean the

manifold assembly.