<B1. System Installation Specifications>

B1-1

IM 01W02D02-01EN

Part-B. Installation

This section describes the installation of YFGW610.
Use YFGW610 in the following procedure.
1. Installation of YFGW610
2. Wiring of the power supply, ground and network cable

B1. System Installation Specifications

The system must be installed in an appropriate environment to ensure stable system operation.
The following defines the detailed specifications of YFGW610 installation environment.

Table B1-1 System installation specifications

Item

Specifications

Applicable stand-

ards

Ambient

temperature

Operating

-40 to 65°C (at altitude below 2000

meters)
-40 to 55°C (at altitude between 2000

and 3000 meters)

Transport /storage

-40 to 85°C

Ambient humidity

Operating

5 to 95% relative (without condensing)

Transport /storage

5 to 95% relative (without condensing)

Temperature

gradient

Operating

Within +/-10°C per hour

JEIDA 29 Class B

Transport /storage

Within +/-20°C per hour

Protection class

IP20

IEC529

Vibration resistance

0.15 mm P-P (5 to 58 Hz)

IEC68-2-6

1 G (58 to 150 Hz)

Impact resistance

15 G, 11 msec (no conductive, and 3-di-

rection half sine waves)

IEC68-2-27

Altitude

Up to 3000 meters (due to restricted

ambient temperature)

Noise level

Electric field

3 V/m or less (80 MHz to 1 GHz)

Electrostatic

discharge

4 kV or less (contact discharge), 8 kV or

less (aerial discharge)

Grounding

Class D grounding (100 ohms or less)

Cooling

Natural cooling

Mounting

Mounted on DIN rails

Power supply

Voltage range

10.8 to 26.4 V DC

Rated voltage

24 V DC

Allowable ripple

Less than 1% p-p

Power consumption

10 W