B4-5, Important – Yokogawa YFGW610 User Manual
Page 31

<B4. Power, ground, and signal cable connection>
B4-5
IM 01W02D02-01EN
Table B4-1 List of power supply cables
Cable
Dimensions (mm)
Phoenix Contact's
type
Section
area
(mm
2
)
AWG
Strip
length
(mm)
I
1
I
2
d
1
S
1
d
2
S
2
0.25
24
10
10.5
6.0
0.8
0.15
2.0
0.25
AI 0.25-6 BU
0.34
22
10
10.5
6.0
0.8
0.15
2.0
0.25
AI 0.34-6 TQ
10
12.5
8.0
0.8
0.15
2.0
0.25
AI 0.34-8 TQ
0.5
20
10
12.0
6.0
1.1
0.15
2.5
0.25
AI 0.5-6 WH
10
14.0
8.0
1.1
0.15
2.5
0.25
AI 0.5-8 WH
10
16.0
10.0
1.1
0.15
2.5
0.25
AI 0.5-10 WH
0.75
20
10
12.0
6.0
1.3
0.15
2.8
0.25
AI 0.75-6 GY
10
14.0
8.0
1.3
0.15
2.8
0.25
AI 0.75-8 GY
10
16.0
10.0
1.3
0.15
2.8
0.25
AI 0.75-10 GY
1.0
18
10
12.0
6.0
1.5
0.15
3.0
0.3
AI 1-6 RD
10
14.0
8.0
1.5
0.15
3.0
0.3
AI 1-8 RD
10
16.0
10.0
1.5
0.15
3.0
0.3
AI 1-10 RD
1.5
16
10
12.0
6.0
1.8
0.15
3.4
0.3
AI 1.5-6 BK
10
14.0
8.0
1.8
0.15
3.4
0.3
AI 1.5-8 BK
10
18.0
10.0
1.8
0.15
3.4
0.3
AI 1.5-10 BK
2.5
14
10
14.0
8.0
2.3
0.15
4.2
0.3
AI 2.5-8 BU
10
16.0
10.0
2.3
0.15
4.2
0.3
AI 2.5-10 BU
IMPORTANT
• Use the same manufacturer for sleeves and tools.
• Use sleeve tools that match the wire thickness.
• Insert the wire to be connected completely into the pressure clamp terminal and attach it
securely.
• Secure the cable to cable clamps, etc. so that the weight of the cable applied to the terminal
is minimized.