Handling conflict messages, Handling conflict messages -11 – Yokogawa FieldMate User Manual

Page 20

Advertising
background image

<3 PRM Synchronization Tool start>

3-11

IM 01R01A20-01E

8th Edition : May 31, 2013-00

TIP

You can also stop the activity at any point in time. To stop the activity, click [Stop] in the Synchronize Devices in

Progress dialog box. When an activity is stopped, the process is halted but the information that was processed

before stopping the activity will not be reverted.

11. When the activity is finished, click [Close].

Handling conflict messages

During the synchronization activity, the Conflict Message dialog box appears when the device

information from FieldMate is older than the device information in PRM or when both PRM and

FieldMate have new information.

Table3-3

Situations that trigger the Conflict Message

PRM Timestamp

FieldMate Timestamp

Result

Same

Same

None

Newer

Older

Conflict Message appears.

Older

Newer

Automatic overwrite from FieldMate to PRM.

Newer

Newer

Conflict Message appears.

030307E.ai

Figure3-7

Conflict Message dialog box

To resolve conflicts, click the following options:

• [PRM Data] to overwrite FieldMate data with PRM data for all devices.
• [FieldMate Data] to overwrite PRM data with FieldMate data for all devices.
• [Latest Data] to overwrite FieldMate older data with PRM newer data, comparing with the

latest Update Date.

• [Prompt] to select the overwrite direction for the current device only.
• [Continue] to apply the selected conflict resolution and proceed with the synchronization

activity.

• [Stop] to stop the synchronization activity.

NOTE

If an option is not selected within 30 minutes, the data transfer will skip the affected device and

proceed with the transfer for the remaining devices.